Instrumentation Cables 

  EN 50288-7 Instrumentation Cables PE Insulated, LSZH Sheathed, Individual & Overall Screened, Armoured Instrumentation Cables (Multitriple)

RE-2Y(St)HSWAH-TiMF 70°C / 300 V

EN 50288-7 Instrumentation Cables

STANDARDS
Basic design to EN50288-7

APPLICATION: 
These cables are used for transmission of analoge and digital signals in instrument and control systems at
 chemistry and  petr°Chemistry industry plants, power plants, natural gas and petroluem plants, etc... 
These cables are used in the environments which have no corrosive gases are emitted in the event of fire.
 In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is
 extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, 
e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables
 are not recommended for direct burial. They are for indoor  and outdoor installation, in dry and wet l°Cations; 
on racks, trays, in conduits.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); 
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation   (Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; 
CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; 
CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; 
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.

VOLTAGE RATING
300V  

CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: PE compound, EN 50290. 2-23.
Individual Screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²
Pair:Two conductors twisted to form a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: HFFR compound, EN 50290-2-27
Armour: Galvenized round steel wire, EN 10257-1
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type
SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and  anti termite properties can be offered as option.

COLOUR CODE
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.
Outer Sheath: Black or blue for intrinsically safe systems 

Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +70°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 10 X Overall Diameter 

CONSTRUCTION PARAMETERS

Cable Code

RE-2Y(St)HSWAH-TiMF

No. of Triples 3xCross
 Section

Nominal Insulation Thick-ness

Nominal Inner Sheath Thick-ness

Nominal 
Overall  Diameter 
Over Inner  
Sheath
Nominal 
Armour 
Wire 
Diameter

Nominal
Outer
Sheath
Thick
-ness

Nominal 
OverallDiameter
Approx. 
Weight

No.x3xmm2

mm

mm

mm mm

mm

mm kg/km

0.5mm2, Multitriple 

RE-2Y(St)HSWAH-TiMF 2T0.5

2x3x0.5

0.35

1.0

9.7 0.9

1.4

14.3 363

RE-2Y(St)HSWAH-TiMF 4T0.5

4x3x0.5

0.35

1.0

11.1 0.9

1.4

15.7 456

RE-2Y(St)HSWAH-TiMF 5T0.5

5x3x0.5

0.35

1.1

12.4 0.9

1.5

17.2 517

RE-2Y(St)HSWAH-TiMF 6T0.5

6x3x0.5

0.35

1.1

14.0 0.9

1.5

18.8 612

RE-2Y(St)HSWAH-TiMF 8T0.5

8x3x0.5

0.35

1.1

14.9 0.9

1.5

19.7 800

RE-2Y(St)HSWAH-TiMF 10T0.5

10x3x0.5

0.35

1.2

17.0 1.25

1.6

22.7 951

RE-2Y(St)HSWAH-TiMF 12T0.5

12x3x0.5

0.35

1.2

17.6 1.25

1.6

23.3 978

RE-2Y(St)HSWAH-TiMF 16T0.5

16x3x0.5

0.35

1.3

20.1 1.25

1.7

26.0 1201

RE-2Y(St)HSWAH-TiMF 20T0.5

20x3x0.5

0.35

1.4

22.3 1.25

1.7

28.2 1394

RE-2Y(St)HSWAH-TiMF 24T0.5

24x3x0.5

0.35

1.5

24.4 1.25

1.8

30.5 1607

0.75mm2, Multitriple 

RE-2Y(St)HSWAH-TiMF 2T0.75

2x3x0.75

0.38

1.0

10.6 0.9

1.4

15.2 418

RE-2Y(St)HSWAH-TiMF 4T0.75

4x3x0.75

0.38

1.1

12.4 0.9

1.5

17.2 521

RE-2Y(St)HSWAH-TiMF 5T0.75

5x3x0.75

0.38

1.1

13.7 0.9

1.5

18.5 608

RE-2Y(St)HSWAH-TiMF 6T0.75

6x3x0.75

0.38

1.1

15.4 0.9

1.5

20.2 820

RE-2Y(St)HSWAH-TiMF 8T0.75

8x3x0.75

0.38

1.2

16.7 0.9

1.6

21.7 942

RE-2Y(St)HSWAH-TiMF 10T0.75

10x3x0.75

0.38

1.3

19.0 1.25

1.6

24.7 1104

RE-2Y(St)HSWAH-TiMF 12T0.75

12x3x0.75

0.38

1.3

19.7 1.25

1.7

25.6 1178

RE-2Y(St)HSWAH-TiMF 16T0.75

16x3x0.75

0.38

1.4

22.5 1.25

1.7

28.4 1441

RE-2Y(St)HSWAH-TiMF 20T0.75

20x3x0.75

0.38

1.5

24.9 1.25

1.8

31.0 1888

RE-2Y(St)HSWAH-TiMF 24T0.75

24x3x0.75

0.38>

1.6

27.2 1.25

1.9

33.5 2168

1.0mm2, Multitriple 

RE-2Y(St)HSWAH-TiMF 2T1.0

2x3x1

0.4

1.0

11.5 0.9

1.4

16.1 472

RE-2Y(St)HSWAH-TiMF 4T1.0

4x3x1

0.4

1.1

13.4 0.9

1.5

18.2 597

RE-2Y(St)HSWAH-TiMF 5T1.0

5x3x1

0.4

1.1

14.8 0.9

1.5

19.6 689

RE-2Y(St)HSWAH-TiMF 6T1.0

6x3x1

0.4

1.2

16.9 0.9

1.5

21.7 940

RE-2Y(St)HSWAH-TiMF 8T1.0

8x3x1

0.4

1.2

18.1 1.25

1.6

23.8 1035

RE-2Y(St)HSWAH-TiMF 10T1.0

10x3x1

0.4

1.3

20.7 1.25

1.7

26.6 1279

RE-2Y(St)HSWAH-TiMF 12T1.0

12x3x1

0.4

1.3

21.4 1.25

1.7

27.3 1383

RE-2Y(St)HSWAH-TiMF 16T1.0

16x3x1

0.4

1.4

24.4 1.25

1.7

30.3 1689

RE-2Y(St)HSWAH-TiMF 20T1.0

20x3x1

0.4

1.5

27.1 1.25

1.8

33.2 2204

RE-2Y(St)HSWAH-TiMF 24T1.0

24x3x1

0.4

1.6

29.6 1.6

1.9

36.6 2509

1.3mm2, Multitriple 

RE-2Y(St)HSWAH-TiMF 2T1.3

2x3x1,3

0.45

1.1

12.8 0.9

1.5

17.6 532

RE-2Y(St)HSWAH-TiMF 4T1.3

4x3x1,3

0.45

1.1

14.7 0.9

1.5

19.5 685

RE-2Y(St)HSWAH-TiMF 5T1.3

5x3x1,3

0.45

1.2

16.5 0.9

1.6

21.5 925

RE-2Y(St)HSWAH-TiMF 6T1.3

6x3x1,3

0.45

1.3

18.8 1.25

1.6

24.5 1090

RE-2Y(St)HSWAH-TiMF 8T1.3

8x3x1,3

0.45

1.3

20.1 1.25

1.7

26.0 1250

RE-2Y(St)HSWAH-TiMF 10T1.3

10x3x1,3

0.45

1.4

23.0 1.25

1.8

29.1 1484

RE-2Y(St)HSWAH-TiMF 12T1.3

12x3x1,3

0.45

1.5

24.0 1.25

1.8

30.1 1595

RE-2Y(St)HSWAH-TiMF 16T1.3

16x3x1,3

0.45

1.6

27.4 1.25

1.9

33.7 2225

RE-2Y(St)HSWAH-TiMF 20T1.3

20x3x1,3

0.45

1.7

30.4 1.6

2.0

37.6 2596

RE-2Y(St)HSWAH-TiMF 24T1.3

24x3x1,3

0.45

1.8

33.1 1.6

2.0

40.3 2962

RE-2Y(St)HSWAH-TiMF 2T1.5

2x3x1,5

0.45

1.1

13.2 0.9

1.5

18.0 561

RE-2Y(St)HSWAH-TiMF 4T1.5

4x3x1,5

0.45

1.2

15.4 0.9

1.5

20.2 818

RE-2Y(St)HSWAH-TiMF 5T1.5

5x3x1,5

0.45

1.2

17.1 1.25

1.6

22.8 999

RE-2Y(St)HSWAH-TiMF 6T1.5

6x3x1,5

0.45

1.3

19.5 1.25

1.6

25.2 1164

RE-2Y(St)HSWAH-TiMF 8T1.5

8x3x1,5

0.45

1.4

21.1 1.25

1.7

27.0 1354

RE-2Y(St)HSWAH-TiMF 10T1.5

10x3x1,5

0.45

1.5

24.1 1.25

1.8

30.2 1596

RE-2Y(St)HSWAH-TiMF 12T1.5

12x3x1,5

0.45

1.5

24.9 1.25

1.8

31.0 1953

RE-2Y(St)HSWAH-TiMF 16T1.5

16x3x1,5

0.45

1.6

28.4 1.6

1.9

35.4 2388

RE-2Y(St)HSWAH-TiMF 20T1.5

20x3x1,5

0.45

1.7

31.6 1.6

2.0

38.8 2800

RE-2Y(St)HSWAH-TiMF 24T1.5

24x3x1,5

0.45

1.8

34.4 1.6

2.1

41.8 3100

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size   mm 2  

0.5 

0.75  

1.0  

1.3

1.5  

Insulation thickness (nominal) mm

0.4

0.4

0.4

0.45

0.45

Conductor resistance (20°C)   Ω/km 

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz)  pF/m(Max.) 115
Inductance mH/km(Max.) 1
Capacitance unbalance(1 kHz)  pF/500 m (Max.) 500 
L / R (ratio) (max.) μH/Ω

25

25

25

40

40

Operating voltage Urms V 300
Test Voltage  Core to Core  1500 
Core to Screen  1500